Stability Improvement by FACTS Devices: A Comparison between STATCOM and SSSC in 500 kV Grid Subsystem
Bagus Chandra Wibawa, Haidar Ali, Rudy Setiabudy, Fauzan Hanif Jufri, Faiz Husnayain

Universitas Indonesia


Abstract

Loss of 500 kV transmission line of Paiton-Grati 1 & 2 causes voltage instability in surrounding subsystem which may lead to further disturbance in the Jawa-Bali system. Minimization of the voltage instability can be handled by adding Flexible AC Transmission System (FACTS) devices, such as Static Synchronous Compensator (STATCOM) and Static Synchronous Series Compensator (SSSC). STATCOM and SSSC have the capability of dynamically controlling the power flow through a line. This paper aims to compare the performance of both devices to maintain system stability in the case of loss of 500kV transmission line. The performance of these methods is compared through the analysis of the bus voltage, the active power, and the rotor angle. As a result, this paper shows that the implementation of STATCOM is more stable instead of SSSC.

Keywords: FACTS, Instability, SSSC, STATCOM

Topic: Electrical Engineering

Link: https://ifory.id/abstract/bqKT2kPjGMr7

Conference: Broad Exposure on Science and Technology (BEST 2019)

Plain Format | Corresponding Author (Dwi Riana Aryani)

Featured Events

<< Swipe >>
<< Swipe >>

Embed Logo

If your conference is listed in our system, please put our logo somewhere in your website. Simply copy-paste the HTML code below to your website (ask your web admin):

<a target="_blank" href="https://ifory.id"><img src="https://ifory.id/ifory.png" title="Ifory - Indonesia Conference Directory" width="150" height="" border="0"></a>

Site Stats