Level and Temperature Monitoring System In Blending Process Using Zigbee Wireless Sensor Network Astrie Kusuma Dewi(a*), Andrian Aziz Burhan Abid Sahaya (a), Wahid Sugiman (a)
a) Polytechnic of Energy and Mineral Akamigas, Jalan Gajah Mada No 38, Cepu, Blora, Jawa Tengah 58315, Indonesia *astrie.dewi[at]esdm.go.id
Abstract
The use of cable transmission media has several drawbacks related to distance problems, geographical factors, the initial cost of procurement is quite expensive, and the arrangement of the cables is not practical. Wireless based systems appear to answer these challenges, one of which is the Wireless Sensor Network (WSN). In the industrial field the use of WSN is quite extensive in the field of monitoring and measurement. This study implements WSN technology for monitoring levels and temperatures in the Zigbee Wireless Network Sensor blending process. The implementation uses the Atmega 328 Arduino Uno, Xbee Pro and LabView 2017 microcontroller as its Human Machine Interface. Using statistical analysis methods paired t test and linear regression to analyze how the error rate and correlation of the observed variables. Based on the results of the study obtained correlations of level and temperature measurements respectively 99.97% for level measurements and 99.98% for temperature measurements. The average relative error is 2.76% for level measurements and 0.65% for temperature measurements. Tests are carried out to measure the level in the range 0 -40 cm and temperatures 26oC - 70oC with ultrasonic sensors and LM35.